Box Fill Calculator NEC 314.16

Calculate required box volume per NEC 314.16(B) counting rules.

Cable mode: Enter cables entering the box (e.g., "two 14/2 NM-B"). Conductors are auto-counted — each cable's hot and neutral count as individual conductors. Equipment grounds are counted per 314.16(B)(5): 1–4 EGCs = 1 conductor volume; each EGC beyond 4 adds ¼ conductor volume.

Cables Entering Box

Pigtail reminder: Pigtails and jumpers that originate and terminate inside the box are NOT counted for box fill. Only conductors that enter through a cable or raceway count. This is the #1 box fill mistake.

By clicking Apply, you acknowledge that results are for reference only and must be verified by a qualified electrician against the current National Electrical Code and local amendments.

--
Minimum Box Volume Required
ItemCountVolume EachSubtotal

Recommended Box

--

For reference only. Verify all results with the current NEC and local amendments. See Terms of Use.