Tables › Raceway Fill

Raceway Fill Quick Chart NEC Ch.9 T.4

Maximum number of same-size THHN/THWN conductors in trade-size conduit at 40% fill.

EMT — Electrical Metallic Tubing

Wire Size 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 4"
14 AWG1222356184138241364598
12 AWG916264664104182275452
10 AWG51016283964112169278
8 AWG3691622366496158
6 AWG2471216264669114
4 AWG12471016284370
3 AWG1146814243660
2 AWG1135711203050
1 AWG111458152237
1/011347121931
2/011246101626
3/01123591322
4/01112471118
250 kcmil11236915
300 kcmil11135813
350 kcmil11124711
400 kcmil1124610
500 kcmil111358

IMC — Intermediate Metal Conduit

Wire Size 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 4"
14 AWG1628437598163251390629
12 AWG1221335775124190296477
10 AWG71320354676117182293
8 AWG471220264367104167
6 AWG3581419314875121
4 AWG13591219304675
3 AWG13471016253963
2 AWG1246814213353
1 AWG1124610152439
1/0112458132033
2/011347111727
3/01123691422
4/01123571118
250 kcmil11246915
300 kcmil11135813
350 kcmil11134711
400 kcmil11124610
500 kcmil112358

RMC — Rigid Metal Conduit

Wire Size 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 4"
14 AWG1322366385141227346570
12 AWG1017284865107172263433
10 AWG61017294066106161266
8 AWG36101723376092151
6 AWG2471216274467110
4 AWG13481017274268
3 AWG1246914233558
2 AWG1235712193049
1 AWG112459142135
1/011347121830
2/011346101525
3/01123581220
4/01112471017
250 kcmil11235814
300 kcmil11135712
350 kcmil11124610
400 kcmil112359
500 kcmil111347
Fill Percentages
1 conductor = 53% fill allowed. 2 conductors = 31% fill. 3 or more conductors = 40% fill. These percentages come from NEC Chapter 9, Table 1.
Mixed Wire Sizes?
This chart is for same-size conductors only. For mixed wire sizes, use the Conduit Fill Calculator which computes actual cross-sectional areas.

Values shown are for THHN/THWN insulation type. Other insulation types have different outer diameters and will yield different fill counts.

For reference only. Verify all results with the current NEC and local amendments. See Terms of Use.