Single-Phase Motors (NEC 430.248)
| HP | 115V | 200V | 208V | 230V |
|---|---|---|---|---|
| 1/6 | 4.4 | 2.5 | 2.4 | 2.2 |
| 1/4 | 5.8 | 3.3 | 3.2 | 2.9 |
| 1/3 | 7.2 | 4.1 | 4.0 | 3.6 |
| 1/2 | 9.8 | 5.6 | 5.4 | 4.9 |
| 3/4 | 13.8 | 7.9 | 7.6 | 6.9 |
| 1 | 16 | 9.2 | 8.8 | 8 |
| 1-1/2 | 20 | 11.5 | 11 | 10 |
| 2 | 24 | 13.8 | 13.2 | 12 |
| 3 | 34 | 19.6 | 18.7 | 17 |
| 5 | 56 | 32.2 | 30.8 | 28 |
| 7-1/2 | 80 | 46 | 44 | 40 |
| 10 | 100 | 57.5 | 55 | 50 |
Three-Phase Motors (NEC 430.250)
| HP | 200V | 208V | 230V | 460V | 575V |
|---|---|---|---|---|---|
| 1/2 | 2.5 | 2.4 | 2.1 | 1.1 | 0.8 |
| 3/4 | 3.7 | 3.5 | 3.1 | 1.6 | 1.3 |
| 1 | 4.8 | 4.6 | 4.2 | 2.1 | 1.7 |
| 1-1/2 | 6.9 | 6.6 | 6.0 | 3.0 | 2.4 |
| 2 | 7.8 | 7.5 | 6.8 | 3.4 | 2.7 |
| 3 | 11.0 | 10.6 | 9.6 | 4.8 | 3.9 |
| 5 | 17.5 | 16.7 | 15.2 | 7.6 | 6.1 |
| 7-1/2 | 25.3 | 24.2 | 22 | 11 | 9 |
| 10 | 32.2 | 30.8 | 28 | 14 | 11 |
| 15 | 48.3 | 46.2 | 42 | 21 | 17 |
| 20 | 62.1 | 59.4 | 54 | 27 | 22 |
| 25 | 78.2 | 74.8 | 68 | 34 | 27 |
| 30 | 92 | 88 | 80 | 40 | 32 |
| 40 | 120 | 114 | 104 | 52 | 41 |
| 50 | 150 | 143 | 130 | 65 | 52 |
| 60 | 177 | 169 | 154 | 77 | 62 |
| 75 | 221 | 211 | 192 | 96 | 77 |
| 100 | 285 | 273 | 248 | 124 | 99 |
| 125 | 359 | 343 | 312 | 156 | 125 |
| 150 | 414 | 396 | 360 | 180 | 144 |
| 200 | 552 | 528 | 480 | 240 | 192 |
Field Note
Use these values for sizing conductors and overcurrent protection — not the motor nameplate FLA. NEC 430.6(A)(1) requires using these tables instead of nameplate current for conductor sizing and overcurrent protection.
Use these values for sizing conductors and overcurrent protection — not the motor nameplate FLA. NEC 430.6(A)(1) requires using these tables instead of nameplate current for conductor sizing and overcurrent protection.
Next Step
Got your FLA? Use the Wire Size Calculator to find the right conductor.
Got your FLA? Use the Wire Size Calculator to find the right conductor.
For reference only. Verify all results with the current NEC and local amendments. See Terms of Use.