Tables › EGC Sizing

Equipment Grounding Conductor Sizing NEC 250.122

Minimum size equipment grounding conductor for each overcurrent device rating.

Overcurrent Device Rating (Amps) Copper EGC Aluminum or Cu-Clad Al EGC
15 14 AWG 12 AWG
20 12 AWG 10 AWG
30 10 AWG 8 AWG
40 10 AWG 8 AWG
60 10 AWG 8 AWG
100 8 AWG 6 AWG
200 6 AWG 4 AWG
300 4 AWG 2 AWG
400 3 AWG 1 AWG
500 2 AWG 1/0 AWG
600 1 AWG 2/0 AWG
800 1/0 AWG 3/0 AWG
1000 2/0 AWG 4/0 AWG
1200 3/0 AWG 250 kcmil
1600 4/0 AWG 350 kcmil
2000 250 kcmil 400 kcmil
2500 350 kcmil 600 kcmil
3000 400 kcmil 600 kcmil
4000 500 kcmil 800 kcmil
5000 700 kcmil 1200 kcmil
6000 800 kcmil 1200 kcmil
250.122(B) — Upsizing Rule
When ungrounded conductors are increased in size for voltage drop, the equipment grounding conductor must be increased proportionally. Multiply the EGC size by the same ratio: (circular mils of actual conductor) ÷ (circular mils of minimum required conductor).
Common Mistake
The EGC is sized based on the overcurrent device rating, not the wire size. A #10 wire on a 30A breaker requires a #10 copper EGC — but a #10 wire on a 20A breaker only requires a #12 copper EGC.
Conduit as EGC
Listed metallic raceways (EMT, IMC, RMC) can serve as the equipment grounding conductor per NEC 250.118. No separate EGC wire is required when using these raceways, though many electricians pull one anyway as a best practice.

For reference only. Verify all results with the current NEC and local amendments. See Terms of Use.