Tables › Conductor Ampacity

Conductor Ampacity NEC 310.16

Allowable ampacities for insulated conductors rated up to 2000V. Not more than 3 current-carrying conductors in raceway, cable, or earth.

Copper Conductors

Size (AWG/kcmil) 60°C (TW, UF) 75°C (THW, THWN, XHHW) 90°C (THHN, THWN-2, XHHW-2)
14 AWG152025
12 AWG202530
10 AWG303540
8 AWG405055
6 AWG556575
4 AWG708595
3 AWG85100115
2 AWG95115130
1 AWG110130145
1/0 AWG125150170
2/0 AWG145175195
3/0 AWG165200225
4/0 AWG195230260
250 kcmil215255290
300 kcmil240285320
350 kcmil260310350
400 kcmil280335380
500 kcmil320380430
600 kcmil350420475
700 kcmil385460520
750 kcmil400475535
800 kcmil410490555
900 kcmil435520585
1000 kcmil455545615
1250 kcmil495590665
1500 kcmil520625705
1750 kcmil545650735
2000 kcmil560665750

Aluminum or Copper-Clad Aluminum Conductors

Size (AWG/kcmil) 60°C (TW, UF) 75°C (THW, THWN, XHHW) 90°C (THHN, THWN-2, XHHW-2)
12 AWG152025
10 AWG253035
8 AWG354045
6 AWG405060
4 AWG556575
3 AWG657585
2 AWG7590100
1 AWG85100115
1/0 AWG100120135
2/0 AWG115135150
3/0 AWG130155175
4/0 AWG150180205
250 kcmil170205230
300 kcmil190230260
350 kcmil210250280
400 kcmil225270305
500 kcmil260310350
600 kcmil285340385
700 kcmil310375420
750 kcmil320385435
800 kcmil330395450
900 kcmil355425480
1000 kcmil375445500
1250 kcmil405485545
1500 kcmil435520585
1750 kcmil455545615
2000 kcmil470560630
Important
Most terminations are rated 75°C. Use the 75°C column unless you've verified the terminal rating on both ends. The 90°C column is commonly used only as a starting point for derating calculations per NEC 310.15(B).
Derating Reminder
These values assume no more than 3 current-carrying conductors in raceway or cable. For 4–6 conductors, derate to 80%. For 7–9, derate to 70%. See NEC 310.15(C)(1).

For reference only. Verify all results with the current NEC and local amendments. See Terms of Use.